MİXED OCCUPANCY
PRODUCTION HALL /OFFICES/ LABORATARIES
 
Where different parts of a building or storey of a building are designed for different types of occupancies or used for different purposes at the same time, the exit requirements of the entire building or storey of the building shall be determined on the basis of that type of occupancy or usage having the strictest exit requirements or the exit requirements for each building section shall be determined separately.
Case:1500 m2 production hall (high hazard) and 100 m2 anchillary office ,100 m2 Laborataries. Fully sprinklered.
Occupany load of story
High Hazard Production Hall :Area 1500 m2 ,Occ.Density:10m2/prs Occupand Load=1500/10=150 prs
Offices :Area 100 m2 ,Occ.Density:10m2/prs Occupand Load=100/10=10 prs
Laboraties :Area 100 m2 ,Occ.Density:5 m2/prs Occupand Load=100/5=20 prs
Total Occupancy Load of Story:150+10+20=180 person. We need min two exits.
The position of the exit doors shall be so located that the maximum permissible travel distance from any remote point to the doors shall be based on that of the high hazard production hall , having the stricter requirements in Table 2
Maximum permissible distance for high hazard :35 mt & one-way distance :20 mt (common path)

Maximum permissible distance for office :75 mt & one-way distance :30 mt (common path) .But office exit distances calculated on the base of high hazard.

Maximum permissible distance for office :35 mt & one-way distance :20 mt (common path)
At above diagram for office exit route
Maximum permissible travel distance A to C must be smaller than 35 mt and one-way travel distance A to B must be smaller than 20 mt
At above diagram exit route A to E is not a accepted route due to storage room.
 

 

 
 
Google
 
Web www.iklimnet.com
 
   
  http://www.iklimnet.com
 
Book & Magazine
Interstate Bank Fire
Beverly Hills Club Fire
MGM Fire
Firehause Magazine
Special Fires
Hotel Fires
Ship Fires
Industrial Fires
Warehouse Fires

Restaurant/Nightclub Discotheque-Fires

High Rise Fires
Fires
Fires ABC
Big Building Fires
Book About Fires
Fire Stats
Fire Board

Books About Fires

Hotels
Enviroment
Energy Save
Hotels & Legionella
Green Hotels
Hotel Design Books
Control Software