TABLE 1 - EXIT REQUIREMENTS
Occupancy Type
Maximum Travel Distance Number of Persons Per Unit Width .(50 cm) Minumum Width (m) Max. Dead End (m)
One- way Two-way Door Openings Staircases Corridors &Ramps Stairs Corridors Corridors
Non Sprinklered
Sprinklered
Non Sprinklered
Sprinklered Exit to Outdoor Other Exits &Corridor Doors Non-Sprinklered Sprinklered
High Hazard
10
20
20
35 50 40 30 50 1 1.2 10 20
Industrial Buildings (Factories ,warehouses)
15
25
30
60 100 80 60 100 1 1,2 15 20
Shops,Markets
15
25
45
60 100 80 60 100 1 1.2 15 20
Offices
15
30
45
75 100 80 60 100 1 1.2 15 20
Carparks 15 25 45 60 100 80 60 100 1 1.2 15 20
Assembly Buildings 15 25 45 60 100 80 60 100 1 1.2 15 20
Schools ,Educational Buildings 15 25 45 60 100 80 60 100 1 1.5 15 20
Hospitals ,Healthcare facilitiy 15 25 30 60 30 80 15 30 1 2 15 20
Hotels,Hostels,Dormitories 15 20 30 60 60 60 45 50 1 1.2 15 20
Apartmants 15 30 30 75 50 40 30 50 1 1.2 15 20
Apartmants (External Corridor ) 20 40 45 75 50 40 30 50 1 1.2 15 20
                         

 

 
 
Google
 
Web www.iklim.com
 
   
 
  http://www.iklimnet.com
 
Book & Magazine
Interstate Bank Fire
Beverly Hills Club Fire
MGM Fire
Firehause Magazine
Special Fires
Hotel Fires
Ship Fires
Industrial Fires
Warehouse Fires

Restaurant/Nightclub Discotheque-Fires

High Rise Fires
Fires
Fires ABC
Big Building Fires
Book About Fires
Fire Stats
Fire Board

Books About Fires

Hotels
Enviroment
Energy Save
Hotels & Legionella
Green Hotels
Hotel Design Books
Control Software