FIRE EGRESS UNACCEPTABLE EXIT ROUTES |
|
3-Exits should not pass through storage rooms |
|
Exit route A to B is Ok but routes A to C and A to D is not OK.Route A to C and A to D passes from storage areas. |
Production Hall Area :1500 m2 |
Occupant Density:10 m2/pearson. |
Occupant Load :!500/10=150 persons. |
Productioın Hall needs an another exit because occupant load more than 50 persons. |
Diagonal distance of Hall=60 mt . |
Distance between exits for sprinklered building =60/3=20 mt for non-sprinklered building=60/2 =30 mt |
Max Travel Distance for sprinklered building MTD=60 mt ( common path max 25 mt ) and for non-sprinklered building MTD=25 mt ( common path max 15 mt ) |
Productıon of high hazard goods |