Primary Air Systems
PRIMARY AIR SYSTEMS
. Some primary air systems operate with 100% outdoor air at all
times. Systems
using return air should have provision for operating with 100%
out<
door air to reduce operating cost during certain seasons. In some
systems, when the quantity of primary air supplied exceeds the
ventilation or exhaust required, the excess air is recirculated
by a return
system common with the interior system. A quality filter is desirable
in the central air treatment apparatus. If it is necessary to
maintain a given humidity level in cold weather, a humidifier
can usually
be installed. Steam humidifiers have been used successfully. The
water sprays must be operated in conjunction with (1) the preheat
coil elevating the temperature of the incoming air or (2) heaters
in
the spray water circuit.
The cooling coil is usually selected to provide primary air at
a
dew point low enough to dehumidify the system totally. The air
leaves the cooling coil at about 50°F or less, and is almost
completely saturated.
The supply fan should be selected at a point near maximum efficiency
to reduce power consumption, heating of the supply air, and
noise. Sound absorbers may be required at the fan discharge to
attenuate fan noise.
Reheat coils are required in a two-pipe system. Reheat is not
required for the primary air supply of four-pipe systems. Formerly,
many primary air distribution systems for induction units were
designed with 8 to 10 in. of water gage static pressure. With
energy use restrictions, this is no longer economical. Good duct
design and elimination of unnecessary restrictions (for example,
sound traps) can result in primary systems that operate at 4.5
to 6.0 in. of water gage. Primary air distribution systems servicing
fan-coil systems can operate at pressures 1.0 to 1.5 in. lower.
Careful selection of the primary air cooling coil and induction
units for reasonably low air pressure drops is necessary to achieve
a medium-velocity primary air system. Distribution for fan-coil
systems may be low velocity or a combination of low- and medium-velocity
systems.
. Variations in pressure between the first and last terminals
should be minimized to limit the pressure drop across balancing
dampers.
Room sound characteristics vary depending on unit selection,
air system design, and the manufacturer. Units should be selected
by considering the unit manufacturer’s sound power ratings,
the desired maximum room noise level, and the acoustical characteristics
of the room. Limits of sound power level can then be specified
to obtain acceptable acoustical performance.
PERFORMANCE UNDER VARYING LOAD
Under peak load conditions, the psychrometrics of induction unit
and fan-coil unit systems are essentially identical for two-and
four-
pipe systems. The primary air mixes with secondary air conditioned
by the room coil in an induction unit prior to delivery to a room.
Mixing also occurs in a fan-coil unit with a direct-connected
air
supply. If the primary air is supplied to the space separately,
as in
fan-coil systems with independent primary air supplies, the same
effect would occur in the space. The same room conditions result
from two physically independent processes as if the air was directly
connected to the unit.
During cooling, the primary air system provides a portion of
the sensible capacity and all of the dehumidification. The remainder
of the sensible capacity is accomplished by the cooling effect
of the secondary water circulating through the unit cooling coils.
In winter, primary air is provided at a low temperature, and if
humidity control is provided, the air is humidified. All room
heating is supplied by the secondary water system. All factors
that contribute to the cooling load of perimeter space in the
summer, with the exception of the transmission, add heat in the
winter. The transmission factor becomes negative when the outdoor
temperature falls below the room temperature. Its magnitude is
directly proportional to the difference between the room and outdoor
temperatures.
For in-room terminal unit systems, it is important to note that
in
applications where primary air enters at the terminal unit, the
primary air is provided at summer design temperature in winter.
For
systems where primary air does not enter at the terminal unit,
the
primary air should be reset to room temperature in winter. A limited
amount of cooling can be accomplished by the primary air operating
without supplementary cooling from the secondary coil. As long
as
internal heat gains are not high, this amount of cooling is usually
adequate to satisfy east and west exposures during the fall, winter,
and spring, because the solar heat gain is reduced during these
seasons. The north exposure is not a significant factor because
the solar
gain is very low. For the south, southeast, and southwest exposures,
the peak solar heat gain occurs in winter, coincident with a lower
outdoor temperature
In buildings with large areas of glass, the transmitted heat
from
indoors to the outside, coupled with the normal supply of cool
primary air, does not balance internal heat and solar gains until
an outdoor temperature well below freezing is reached. Double-glazed
windows with clear or heat-absorbing glass aggravate this condition
because this type of glass permits constant inflow of solar radiation
during the winter. However, the insulating effect of the double
glass
reduces the reverse transmission; therefore, cooling must be available
at lower outdoor temperatures. In buildings with very high
internal heat gains from lighting or equipment, the need for cooling
from the room coil, as well as from the primary air, can extend
well
into winter. In any case, the changeover temperature at which
the
cooling capacity of the secondary water system is no longer
required for a given space is an important calculation.
|