Ask The HvacMan
Air Grilles
Air Diffusers
Air Quailty
All Air Systems
All Water Systems
Boilers
Building .Managament Systems ..BMS
Burners
CAD
Chillers
Cooling Towers
Cooling Load Calculation
Cryogenics
Energy Saving
Duct
Duct ,Smacna
Dampers ,Air
Dust Collection
Fans
Fire Dampers
Glass Selection
Heating
Heat Exchangers,water
Heat Recovery
Heat Tracing Systems
Hepa Filters
Hvac Applications
Humidifiers / Dehumidifiers
Insulation , Duct
Insulation , Pipe
Insulation , Sound
Nano Tech.,In Building
Occupancy Sensors
Pneumatic Conveying
Piping
Pool Ventilation
Process Piping
Psychrometry
Pumps
Radiant Heating
Refrigerant Systems
Solar Collectors
Sound
Steam Generation
Tables & Charts Gnr.
VAV Sytems
Valves
Ventilation
VRV Systems
STORE
Solar Collectors
Flat Plate Collectors
Evacuated Tube Collectors
Concentrating Collectors
Transpired Collectors
Solar Control Systems
Standalone Systems
Grid Connected Systems
Hybrid Systems
Back-up Systems
Solar Cells
Solar Arrays
Inverters
Change Controller
Turbines
Hybrid Systems
Grid Systems
Water Pumping
Using Wind Energy
Enviromental Aspects
Buyer's Guide
Fire Exit Systems
Save Energy
Solar Water Heating
Solar Electric Systems
Wind Turbines
Passive Solar Heating
Passive Solar Cooling
Building Material
Water Conservation
Ground Source Heat-Pumps
Green Hotels

Glass &Windows Selection

Hotels ,Motels ,Design Criteria
 
 
Space
Design Temperatures & R.Humidity

Occupancy

Ventilation

Lighting Load

Nots
Cooling 'C
Heating 'C
m2/person
m2/person
watt/m2
             
Guestrooms
22 / %50 rH
24
2
 
Guestroom Corridors
22 / %50 rH
21
11
 
Service Corridors
24 / %50 rH
21
2.8
17
32
Under negative pressure
Garages           Min 8 air change
Exec.Lounge
22 / %50 rH
21
2.3
25
32
 
Administrative Office
22 / %50 rH
21
9.3
42
43
 
Employee Cafeteria
24 / %50 rH
21
0.9
25
32
Under negative pressure
Kitchens
27 / %50 rH
21
4.6
50
32
 
Main lobby/entrance
22 / %50 rH
21
3.3
17
43
 
Lounge
22 / %50 rH
21
0.9
50
54
Under negative pressure
Businnes Center
22 / %50 rH
21
4.6
25
75
 
Fitness Center
22 / %50 rH
21
4.2
34
32
Under negative pressure
Ballrooms
22 / %50 rH
21
0.9
34
86
 
Meeting Rooms
22 / %50 rH
21
1.4
34
65
 
Indoor Pool
26.5 / %65 rH
26.5
6
34
32
Under negative pressure
Hause Keeping
25 / %50 rH
21
4.6
25
32
 
Mechanical Rooms
25 / %50 rH
21
       
Laundry
26.5 / %65 rH
18
7.4
50
32
Under negative pressure
Pastry Shop
18 / %50 rH
18
4.6
50
32
 
Computer Room
24 / %50 rH
21
      11 Kw Eq.load
Restaurants
22 / %50 rH
21
1.4
17
54
 
             
 
 
 