Ask The HvacMan
Air Grilles
Air Diffusers
Air Quailty
All Air Systems
All Water Systems
Boilers
Building .Managament Systems ..BMS
Burners
CAD
Chillers
Cooling Towers
Cooling Load Calculation
Cryogenics
Energy Saving
Duct
Duct ,Smacna
Dampers ,Air
Dust Collection
Fans
Fire Dampers
Glass Selection
Heating
Heat Exchangers,water
Heat Recovery
Heat Tracing Systems
Hepa Filters
Hvac Applications
Humidifiers / Dehumidifiers
Insulation , Duct
Insulation , Pipe
Insulation , Sound
Nano Tech.,In Building
Occupancy Sensors
Pneumatic Conveying
Piping
Pool Ventilation
Process Piping
Psychrometry
Pumps
Radiant Heating
Refrigerant Systems
Solar Collectors
Sound
Steam Generation
Tables & Charts Gnr.
VAV Sytems
Valves
Ventilation
VRV Systems
STORE
Solar Collectors
Flat Plate Collectors
Evacuated Tube Collectors
Concentrating Collectors
Transpired Collectors
Solar Control Systems
Standalone Systems
Grid Connected Systems
Hybrid Systems
Back-up Systems
Solar Cells
Solar Arrays
Inverters
Change Controller
Turbines
Hybrid Systems
Grid Systems
Water Pumping
Using Wind Energy
Enviromental Aspects
Buyer's Guide
Fire Exit Systems
Save Energy
Solar Water Heating
Solar Electric Systems
Wind Turbines
Passive Solar Heating
Passive Solar Cooling
Building Material
Water Conservation
Ground Source Heat-Pumps
Green Hotels

Glass &Windows Selection

Water source heat pump (WSHP) systems design
 

1-Establish block heating and cooling load of building .

This should be calculated by the methods shown in the ASHRAE “Handbook of Fundamentals.” Enter block cool- ing load on design worksheet. A sample worksheet appears in Chapter 8.

2-Establish block heating and cooling load of building .

This should be calculated by the methods shown in the ASHRAE “Handbook of Fundamentals.”

 

 

For calculation of heating or cooling load you can use software

 

Cooling Heating Load Calculation Software

 

3-Select all units for building

After computing all heat losses and gains, select terminal heating and cooling units for each room or zone in the building. Select for the greater of the heating or cooling load. Base selection on unit cooling capacities with 100°F (37.8°C) leaving water temperature, or on unit heating capacities with 65°F (18.3°C) leaving water temperature

 

4-Select the evaporative water cooler

Closed circuit cooling towers operate in a manner similar to open cooling towers, except that the heat load to be rejected is transferred from the process fluid (the fluid being cooled) to the ambient air through a heat exchange coil. The coil serves to isolate the process fluid from the outside air, keeping it clean and contaminate free in a closed loop. This creates two separate fluid circuits: (1) an external circuit, in which spray water circulates over the coil and mixes with the outside air, and (2) an internal circuit, in which the process fluid circulates inside the coil. During operation, heat is transferred from the internal circuit, through the coil to the spray water, and then to the atmosphere as a portion of the water evaporates.

Summarize the total rated cooling capacity of all terminal units in kcal/h or kW.

Select evaporative cooler from manufacturer’s data which indicate performance in terms of total capacity vs. summer design wet bulb temperature.

Apply diversity, if other than 80%, to permit selection of proper size cooler. Note that the flow rate remains con stant for a given total connected capacity and wet bulb condition at any diversity.

Never select cooler for 100% diversity (100% of the units running 100% of the time) or cooler selection will be oversized to no benefit. A few
large units will require a larger diversity factor than a sys tem composed of small increments.

Probable diversity factors based on total system flow rate are:

85% for up to 100 total system gpm (6.31 total system L/s) ,(22,7 m3/h)

80% for 100 to 150 total system gpm (6.31 to 9.46 total system L/s) (22,7 to 24m3/h)

75% for over 150 total system gpm (9.46 total system L/s) (24m3/h)

 

 

5-Determine loop water flow

a-Determine outside wet bulb temperature

b- Evaporative water cooler exit water temperature will be 4-8'C higher than wet bulb temperature

c-Use a PHE (plate heat exchanger for loop water from saving freezing in winter times

d-Loop water temperaure will be 2_4'C higher than water cooler temperature.These is your loop nominal water temperature

Example

Wet Bulb Temperature :22'C

Water Exit Temperature of evaporaitve cooler:22'C+4'C =26'C

Water Inlet Temperature of evaporaitve cooler:26'C+6'C =32'C

Loop Water exit temperature of PHe:26'C+4'C =30'C

Loop Water inlet t temperature of PHe:30'C+5'C =35'C

Divide total cooling load capacity by temperature differantials.

do not apply diversity to flow rates

 

 
 

 

 
 
 
 

 

 
 
 
 
Back
 
Back to HvacApplications Main Page
 
Back to Hvac Expert Main Page

 

 

 

 
Google
 
Web www.iklimnet.com
 
 
  http://www.iklimnet.com
 
Hotels
Enviroment
Legionnare Disease
Energy Saving
Control Software
Hotel Design Books

Hotel Design