Ask The HvacMan
Air Grilles
Air Diffusers
Air Quailty
All Air Systems
All Water Systems
Boilers
Building .Managament Systems ..BMS
Burners
Chillers
Cooling Towers
Cooling Load Calculation
Cryogenics
Energy Saving
Duct
Duct ,Smacna
Dampers ,Air
Dust Collection
Fans
Fire Dampers
Glass Selection
Heating
Heat Exchangers,water
Heat Recovery
Heat Tracing Systems
Hepa Filters
Hvac Applications
Humidifiers / Dehumidifiers
Insulation , Duct
Insulation , Pipe
Insulation , Sound
Nano Tech.,In Building
Occupancy Sensors
Pneumatic Conveying
Piping
Pool Ventilation
Process Piping
Psychrometry
Pumps
Radiant Heating
Refrigerant Systems
Solar Collectors
Sound
Steam Generation
Tables & Charts Gnr.
VAV Sytems
Valves
Ventilation
VRV Systems
STORE
Solar Collectors
Flat Plate Collectors
Evacuated Tube Collectors
Concentrating Collectors
Transpired Collectors
Solar Control Systems
Standalone Systems
Grid Connected Systems
Hybrid Systems
Back-up Systems
Solar Cells
Solar Arrays
Inverters
Change Controller
Turbines
Hybrid Systems
Grid Systems
Water Pumping
Using Wind Energy
Enviromental Aspects
Buyer's Guide
 
Save Energy
Solar Water Heating
Solar Electric Systems
Wind Turbines
Passive Solar Heating
Passive Solar Cooling
Building Material
Water Conservation
Ground Source Heat-Pumps
Green Hotels

Glass &Windows Selection

Selection of Sound Silencers


The selection of a silencer can best be demonstrated by using an example. The method can be used irrespective of whether a cylindrical silencer, rectangular silencer or an enclosure needs to be dimensioned.

Specification
A discharge attenuator is required to reduce fan noise to 85 dB(A) at 1 metre.

The Oktavband values of the fan are*:

Oktavband Hz 64 125 250 500 1k 2k 4k 8k
Sound Power Level 108 108 109 115 106 105 100 95

Volume flow rate is 0,97 m3/s
Maximum pressure loss through attenuator to be 125 Pa (N/m2)
* From Sound calculation, e. g. from Witt & Sohn Fan Selection Programm

Step 1

Determine the attenuator insertion loss from SWL and target noise level

Oktavband Hz 63 125 250 500 1K 2K 4K 8K  
Fan Sound Pressure Level dB 108 108 109 115 106 105 100 95 (1)
A´wtg dB -26 -16 -9 -3 0 +1 +1 -1 (2)
SPL @ 1m dB -8 -8 -8 -8 -8 -8 -8 -8 *(3)
Target 85 dB(A)** dB -80 -80 -80 -80 -80 -80 -80 -80 **(4)
Approx. Attenuator insertion loss dB - 4 12 24 18 18 13 6 (1)+(2+3+4)

* Assumes free field conditions (no reflections from the wall) over a hemisphere
** As a guideline: 5 dB less than the target noise level in each oktavband
Step 2

Select attenuator to achieve the required insertion loss
From the attenuator insertion loss tables select an attenuator that has an insertion loss equal to or greater than the required insertion loss in each octave. In this example, the attenuator type 364 has an insertion loss that closely matches the required insertion losses.

Oktavband Hz 64 125 250 500 1k 2k 4k 8k
Required l. Loss dB - 4 12 24 18 18 13 6
Insertion loss of type 364 dB 5 8 16 24 29 26 18 16

Step 3

Checking that the attenuator insertion loss meets the target noise level

Oktavband Hz 64 125 250 500 1k 2k 4k 8k
Fan Sound Pressure Level dB 108 108 109 115 106 105 100 95
A´wtg dB -26 -16 -9 -3 0 +1 +1 -1
SPL @ 1m dB -8 -8 -8 -8 -8 -8 -8 -8
Insertion Loss dB -5 -8 -16 -24 -29 -26 -18 -16
A´wtd SPL @ 1m dB 69 76 76 80 69 72 75 70

Total by normal DB addition = 84 dB(A)

Step 4

Determine attenuator cross section to meet the pressure loss requirement

A maximum of 125 Pa pressure loss was specified. The 'K' factor from attenuator insertion loss tabe - for 364 it is 5.9. From the rectangular attenuator pressure loss graph follow the diagonal 'K' factor line equivalent to 5.9 till it meets the 125 N/m² (horizontal) pressure drop line. From this point go vertically down the graph to the attenuator face velocity in m/sec. In this example, 5.8 m/sec. An attenuator cross section can now be calculated from the required face velocity of 5.8 m/sec and the air volume at 0,97 m3/sec. The (minimum) cross-sectional area in this example is therfore 0,97/58%nbsp;m2 = 0,167 m2.

For a cylindrical attenuator this can be seen directely for the graphs for CPA-1/CPA-2D below.

 

 

 
Google
 
Web www.iklim.com
  Discuss on the Message Board
   
 
  http://www.iklimnet.com
 
Hotels
Enviroment
Legionnare Disease
Energy Saving
Control Software
Hotel Design Books

Hotel Design