System 4 |
3 Way mixing valve with primery pump
|
|
Functions |
|
|
|
-Primery Circuits :constant flow |
|
-Secondary Circuits :variable flow,constant temperatur |
|
-not provided constant temperature in coils |
|
-Coils ,not subjected to freezing |
|
|
|
Balancing |
|
1-Open port A-AB fully |
|
2-Reduce flow with STAD-P for design flow |
|
3-Open port B-AB fully |
|
4-Adjust STAD-B for design flow Throurh STAD-P |
|
|
|
|
|
Return to control
valve selection |
|