Ask The HvacMan
Air Grilles
Air Diffusers
Air Quailty
All Air Systems
All Water Systems
Boilers
Building .Managament Systems ..BMS
Burners
Chillers
Cooling Towers
Cooling Load Calculation
Cryogenics
Energy Saving
Duct
Duct ,Smacna
Dampers ,Air
Dust Collection
Fans
Fire Dampers
Glass Selection
Heating
Heat Exchangers,water
Heat Recovery
Heat Tracing Systems
Hepa Filters
Hvac Applications
Humidifiers / Dehumidifiers
Insulation , Duct
Insulation , Pipe
Insulation , Sound
Nano Tech.,In Building
Occupancy Sensors
Pneumatic Conveying
Piping
Pool Ventilation
Process Piping
Psychrometry
Pumps
Radiant Heating
Refrigerant Systems
Solar Collectors
Sound
Steam Generation
Tables & Charts Gnr.
VAV Sytems
Valves
Ventilation
VRV Systems
STORE
Solar Collectors
Flat Plate Collectors
Evacuated Tube Collectors
Concentrating Collectors
Transpired Collectors
Solar Control Systems
Standalone Systems
Grid Connected Systems
Hybrid Systems
Back-up Systems
Solar Cells
Solar Arrays
Inverters
Change Controller
Turbines
Hybrid Systems
Grid Systems
Water Pumping
Using Wind Energy
Enviromental Aspects
Buyer's Guide
 
Save Energy
Solar Water Heating
Solar Electric Systems
Wind Turbines
Passive Solar Heating
Passive Solar Cooling
Building Material
Water Conservation
Ground Source Heat-Pumps
Green Hotels

Glass &Windows Selection

Coil Loop Recovery Systems 2


Advantages

does not require that the two air streams be adjacent to each other,

several air streams can be used,

has relatively few moving parts -- a small pump and control valve,

relatively space efficient,

the cooling or heating equipment size can be reduced in some cases,

the moisture removal capacity of existing cooling equipment can be improved,

no cross-contamination between air streams.

Disadvantages

adds to the first cost, to the fan power to overcome add coil pressure drop, and for the glycol circulating pump,

requires added glycol pump and piping, expansion tank, and a three-way freeze protection control valve,

requires that the air streams must be relatively clean and may require filtration.

Applications

Increased ventilation air requirements and rising energy prices have stimulated interest in heat recovery systems. With heat recovery, existing system capacity can be increased without adding chiller or boiler capacity. This system is best applied in buildings where most of the supply ventilation air and the exhaust air is in one or two ducts that are not too far apart.

Best Applications

As this system is for sensible heat recovery only, it is best applied in locations where there is a sizable heating season. Projects that require a large percentage of outdoor air can increase system efficiency by transferring heat in the exhaust to either precool or preheat the incoming air.

Possible Applications

Any building where reducing the sensible load on the cooling equipment is advantageous.

Applications to Avoid

Where there are a number of intake or exhaust air ducts that must be piped, the benefits are likely not to offset the higher fan and pump energy and first cost.

Technology Types (Resource)

Coil energy recovery loop systems are highly flexible and well suited to renovation and industrial applications. The system accommodates remote supply and exhaust ducts and allows the simultaneous transfer of energy between multiple sources and uses. An expansion tank must be included to allow fluid expansion and contraction. A closed expansion tank minimizes oxidation when ethylene glycol is used.

Standard finned tube water coils may be used; however, these need to be designed using an accurate simulation model if high effectiveness values and low costs are to be realized. Integrating runaround loops in buildings with variable loads to achieve maximum benefits may require combining the runaround simulation with building energy simulation.

Moisture must not freeze in the exhaust coil air passage. A three-way temperature control valve should be used that prevents the exhaust coil from freezing. The valve is controlled to maintain the temperature of the solution entering the exhaust coil at 30°F or above. This condition is maintained by bypassing some of the warmer solution around the supply air coil. If a dual- purpose valve is used, it can also ensure that a prescribed air temperature from the supply air coil is not exceeded.

Manufacturer's design curves and performance data should be used when selecting coils, face velocities, and pressure drops, but only when the design data are for the same temperature and operating conditions as in the runaround system.

 

 

 
Google
 
Web www.iklim.com
  Discuss on the Message Board
   
 
  http://www.iklimnet.com
 
Hotels
Enviroment
Legionnare Disease
Energy Saving
Control Software
Hotel Design Books

Hotel Design