Ask The HvacMan
Air Grilles
Air Diffusers
Air Quailty
All Air Systems
All Water Systems
Boilers
Building .Managament Systems ..BMS
Burners
Chillers
Cooling Towers
Cooling Load Calculation
Cryogenics
Energy Saving
Duct
Duct ,Smacna
Dampers ,Air
Dust Collection
Fans
Fire Dampers
Glass Selection
Heating
Heat Exchangers,water
Heat Recovery
Heat Tracing Systems
Hepa Filters
Hvac Applications
Humidifiers / Dehumidifiers
Insulation , Duct
Insulation , Pipe
Insulation , Sound
Nano Tech.,In Building
Occupancy Sensors
Pneumatic Conveying
Piping
Pool Ventilation
Process Piping
Psychrometry
Pumps
Radiant Heating
Refrigerant Systems
Solar Collectors
Sound
Steam Generation
Tables & Charts Gnr.
VAV Sytems
Valves
Ventilation
VRV Systems
STORE
Solar Collectors
Flat Plate Collectors
Evacuated Tube Collectors
Concentrating Collectors
Transpired Collectors
Solar Control Systems
Standalone Systems
Grid Connected Systems
Hybrid Systems
Back-up Systems
Solar Cells
Solar Arrays
Inverters
Change Controller
Turbines
Hybrid Systems
Grid Systems
Water Pumping
Using Wind Energy
Enviromental Aspects
Buyer's Guide
 
Save Energy
Solar Water Heating
Solar Electric Systems
Wind Turbines
Passive Solar Heating
Passive Solar Cooling
Building Material
Water Conservation
Ground Source Heat-Pumps
Green Hotels

Glass &Windows Selection

Heat Recovery Wheel Control Systems

You can control HRW systems with individual DDC units or by building control systems.

Wheel Control (Speed Control Signal by Others)

On/Off Control
Rotor will receive power and will operate when the main disconnect is turned on. A modulating signal is required to control the Rotor speed. The controller can be set up for the following input signals: (0-5V, 0-10V, 1-5V, 2-10V, 5-10V, 10-0V, 10-2V, 10-5V, 0-20V Phase cut, 0-20mA, and 4-20mA). The Rotor can be turned on and off remotely by removing white jumper from terminals #5 and #6 in wheel speed control panel and connecting remote switch as indicated.

Rotation Detection and Alarm
A magnet fitted to the periphery of the rotor actuates a pulse sensor once every revolution. Under normal operation the internal contacts are in the energized position (contact closed between #15 and #13). If the drive belt should fail or if the drive stops, after 20 minutes the internal contacts shall close between #15 common and #14 NC), sending a signal to a remote alarm furnished by others.

Automatic Purge
When wheel is at minimum signal or zero recovery, the wheel will automatically run at minimum speed for 10 seconds every 30 minutes to ensure that the rotor surface is kept clean.

Gentle Starting
The control unit soft-starts the wheel, taking approximately 30 seconds to ramp up the wheel to maximum speed. This extends the life of the drive and belt.

RECOMMENDED TEMPERATURE CONTROLS (Control Signal by Others)

Maximum Discharge Temperature Speed Control
The remote modulating signal shall modulate the speed of the rotor to maintain a maximum Supply Air discharge temperature leaving the Rotor (T-SA). As T-SA rises above the recommended setpoint of 58 F, rotor speed is reduced to decrease rotor effectiveness. If T-SA is below setpoint, the rotor runs at maximum speed with maximum recovery.

Summer Mode Control
When the Outside Air temperature (T-OA) rises above the return air temperature (T-RA), the rotor should be run at maximum speed for maximum recovery.

Frost Control
When the exhaust temperature (T-EA) leaving the AIRotor falls below the recommended setpoint of 15oF, the rotor speed is reduced to reduce heat recovery and maintain a minimum exhaust temperature

 

 

 
Google
 
Web www.iklim.com
  Discuss on the Message Board
   
 
  http://www.iklimnet.com
 
Hotels
Enviroment
Legionnare Disease
Energy Saving
Control Software
Hotel Design Books

Hotel Design