Ask The HvacMan
Air Grilles
Air Diffusers
Air Quailty
All Air Systems
All Water Systems
Boilers
Building .Managament Systems ..BMS
Burners
Chillers
Cooling Towers
Cooling Load Calculation
Cryogenics
Energy Saving
Duct
Duct ,Smacna
Dampers ,Air
Dust Collection
Fans
Fire Dampers
Glass Selection
Heating
Heat Exchangers,water
Heat Recovery
Heat Tracing Systems
Hepa Filters
Hvac Applications
Humidifiers / Dehumidifiers
Insulation , Duct
Insulation , Pipe
Insulation , Sound
Nano Tech.,In Building
Occupancy Sensors
Pneumatic Conveying
Piping
Pool Ventilation
Process Piping
Psychrometry
Pumps
Radiant Heating
Refrigerant Systems
Solar Collectors
Sound
Steam Generation
Tables & Charts Gnr.
VAV Sytems
Valves
Ventilation
VRV Systems
STORE
Solar Collectors
Flat Plate Collectors
Evacuated Tube Collectors
Concentrating Collectors
Transpired Collectors
Solar Control Systems
Standalone Systems
Grid Connected Systems
Hybrid Systems
Back-up Systems
Solar Cells
Solar Arrays
Inverters
Change Controller
Turbines
Hybrid Systems
Grid Systems
Water Pumping
Using Wind Energy
Enviromental Aspects
Buyer's Guide
 
Save Energy
Solar Water Heating
Solar Electric Systems
Wind Turbines
Passive Solar Heating
Passive Solar Cooling
Building Material
Water Conservation
Ground Source Heat-Pumps
Green Hotels

Glass &Windows Selection

Sound reduction
Sound reduction can basically be achieved in
two ways: by absorption and by reflection.
There are various stages of sound reduction in a ventilation plant, including:
* Sound reduction in straight ducts
* Sound reduction in ducts with internal sound insulation
* Sound reduction in bends and branch ducts
* Sound reduction in connection with exhaust into the chamber

* Sound reduction through changes in cross section
* Sound reduction through end reflection. At the point where a duct enters a room, part of the

sound is reflected back to the duct. This acts as a sound reduction for the room.

*Sound reduction through room absorption.
The difference between LW - LP can be considered as a sound reduction due to room absorption.

* Sound reduction through sound absorbers. If the natural attenuation in a system is not sufficient, sound absorbers must be added.

The degree of sound reduction as a result of the aforementioned stages can usually be derived from tables, diagrams and the manufacturer’s data. The following will examine sound reduction in ducts with internal insulation since this a simple method of reducing noise. Sound reduction can roughly be estimated as follows:

D = K . O/A . a^1.4 [db/m]
K = correction factor, approx. 0.7 at 250 Hz
O = absorbing circumference (m) A = free duct area
a= absorption coefficient
Q/A will vary with the shape of the valve’s
cross section, and sound reduction can be
enhanced if the cross section is divided into
several ducts. This phenomenon serves as a
basis for inserting so-called bafflers in sound
absorbers to enhance sound reduction.

Sound calculations
Sound calculations to determine the required sound reduction in the main sound absorber installed after a fan or, for example, after a
damper. As a basis, use the room assumed to be most exposed. This is usually the room with the shortest main duct stretch from the fan to
the room. The following sound calculations must then be performed item-by-item as shown in the example below for an injection system.

1. Use the room’s permissible sound pressure
level from the injection system as a basis.
2. First, check that the selected valves meet
the requirement of item 1. If this is in order,
proceed to the next item.
3. The permissible sound pressure level from
the duct system can now be determined by
subtracting the value of item 2 logarithmically
from the value of item 1. As previously shown,
a diagram is used for this purpose.
4. Add sound reduction due to room
absorption to the value of item 3. (Standard
addition)
5. Add sound reduction due to end reflection to
the value of item 4. (Standard subtraction)
Having now proceeded from the room , past
the valve and into the duct system, the value
of item 5 corresponds to the permissible sound
power level in the ducts right after the valve
(since room absorption has been included).

 

6. Sound reduction in the duct, bends,
branches, etc. until the sound source is
reached.
The sum of the values in 5 and 6 (standard
addition) yields the permissible sound power
level just after the sound source.

7. Find the sound source’s sound power level
in the manufacturer’s catalogue.
8. The difference between the values in item 7
and item 6 yields the sound reduction required
in the sound absorber.
A calculation as shown above must be
performed for each individual octave band.
Sound is normally most critical at frequencies
of 250 Hz and 500 Hz. Accordingly, it usually
suffices to perform calculations for these
frequencies.

There is user-friendly software program
available for these types of calculations,
which greatly facilitates the work.

 

 

 
Google
 
Web www.iklim.com
  Discuss on the Message Board
   
 
  http://www.iklimnet.com
 
Hotels
Enviroment
Legionnare Disease
Energy Saving
Control Software
Hotel Design Books

Hotel Design