Run-around coil systems
These systems can recover energy in other ways besides recapturing
the heat in the exhaust air. For example, waste heat in
the process cooling water from the laboratory equipment
can be recovered. Water chiller waste heat can provide domestic
hot water and space heating for laboratories and offices
with a run-around coil system. A high-performance, run-around
energy exchanger can provide a large increase in overall
HVAC system effectiveness from 50 percent to nearly 70 percent,
large returns on investment, typically 33 percent, and short
payback periods of three years. In new building designs
and retrofits, a run-around system can reduce peak heating
and cooling loads as well as total heating and cooling loads.
The run-around system can have a significant impact upon
the boiler and chiller capacity in new HVAC designs.
The coil energy recovery loop cannot transfer moisture
from one airstream to another; however, indirect evaporative
cooling can reduce the exhaust air temperature, which significantly
reduces cooling loads. For the most cost-effective operation,
with equal airflow rates and no condensation, typical effectiveness
values range from 45 to 65%. Highest effectiveness does
not necessarily give the greatest net cost savings.
The following example illustrates the capacity of a typical
system:
A waste heat recovery system is desired to heat 10,000 cfm
of air from a 0°F design outdoor temperature using an
exhaust airstream at dry-bulb temperature of 75°F and
a wet-bulb temperature of 60°F (at 100% effectiveness
a maximum heating load of 810,000 Btuh) Air flows through
identical eight-row coils at a 400 fpm face velocity. A
30% ethylene glycol solution flows through the coils at
26 gpm.
Freeze control typically maintains the heat recovery capacity
constant for outside air temperatures below about 20°F.
This constant output occurs because the valve has to control
the temperature of the fluid entering the exhaust coil to
prevent frosting. Above about 20°F the heating capacity
gradually declines to 0 Btuh at 60°F outdoor air temperature
(OAT). As the exhaust coil is the source of heat and has
a constant airflow rate, entering air temperature, liquid
flow rate, entering fluid temperature (as set by the valve),
and fixed coil parameters, energy recovered must be controlled
to prevent frosting in the exhaust coil. If the coils are
selected for a 50% sensible heat effectiveness at 0°F
OAT, the actual heat recovered is .5 x 810,000 = 405,000
Btuh.
When the three-way control valve operates at outside air
temperatures of 20°F or lower, a maximum of 405,000
Btu/h is recovered. At the 0°F design temperature and
a sensible effectiveness is 50%, the leaving air dry-bulb
temperature is 35.5°F (= 405,000/{10,000 x 1.08)) and
the 75°F exhaust air is cooled to 37.5°F.
Advantages , Disadvantages
,Applications,Applications to Avoid
|