Interstate Bank Building 
                      Fire; 
                    
                       
                        INITIAL 
                            STAGES 
                          At 2222 on the 
                            night of the fire, the buildings two fire pumps were 
                            shut down by the sprinkler contractor, and the combination 
                            standpipe system was drained down to the 58th floor 
                            level to facilitate connecting the new sprinkler system 
                            to the standpipe at that level. Three minutes later, 
                            at 2225, employees of the sprinkler system contractor 
                            heard glass falling and saw light smoke at the ceiling 
                            level on the 5th floor. A manual alarm was pulled 
                            but sounded for only a few seconds. It is believed 
                            that the alarm was silenced by security personnel 
                            on the ground floor. 
                          At 2230, a smoke 
                            detector on the 12th floor was activated and was reset 
                            by security personnel. At 2232, three additional smoke 
                            detectors on the 12th floor were activated and were 
                            again reset by security personnel. At 2234, four smoke 
                            detectors on the 12th floor were activated and reset.There 
                            was heavy exposure of flames to the windows on successive 
                            floors as the fire extended upward from the 12th to 
                            16th floors. The flames were estimated to be lapping 
                            30 feet up the face of the building. The curtain walls, 
                            including windows, spandrel panels, and mullions, 
                            were almost completely destroyed by the fire. There 
                            were no "eyebrows" to stop the exterior 
                            vertical spread, and fireground commanders were concerned 
                            about the possibility of the fire "lapping" 
                            higher to involve additional floors. 
                             | 
                           | 
                       
                     
                   
                    Minor fire extension also occurred via poke-through penetrations 
                      for electricity and communications, via HVAC shafts, and 
                      via heat conduction through the floor slabs. A minor fire 
                      occurred in a storeroom on the 27th floor, ignited by fire 
                      products escaping from an HVAC shaft that originated on 
                      the 12th floor. This fire self-extinguished due to oxygen 
                      deficiency, but could have greatly complicated the situation 
                      if it had continued to burn. The secondary extensions were 
                      minor compared to the perimeter fire spread at the curtain 
                      walls. 
                    The fire extended at a rate estimated at 45 minutes per 
                      floor and burned intensely for approximately 90 minutes 
                      on each level. This resulted in two floors being heavily 
                      involved at any point during the fire. The upward extension 
                      was stopped at the 16th floor level, after completely destroying 
                      four and one-half floors of the building. 
                      