|
|
|
FC 403, Standard for Fire Sprinkler
Systems, November 1994 |
7. System Components
7.1 Types of Systems
- Unless otherwise approved by the FC, sprinkler systems
in a building shall be of the wet-pipe type.
- Wet-pipe systems shall be equipped with alarm check
valves unless specifically approved by the FC.
- A dry-pipe sprinkler system shall be provided where
more than 20 sprinklers are located in a single unheated
area. Either a dry-pipe system or an anti-freeze system
shall be provided where 20 or less sprinklers are located
in a single unheated area.
- A dry-pipe sprinkler system shall be provided in all
buildings where more than 25 % of the sprinklers are located
in unheated portions of the building. Where less than
25 % of the sprinklers are located in unheated portions
of a building, only those sprinklers shall be connected
to a dry-pipe system, the remainder shall be connected
to a wet-pipe system.
- A deluge sprinkler system, with the approval of the
FC, shall be provided in an area where the nature of the
hazard is such to require that upon operation of the sprinkler
system, water will be discharged from all open sprinklers
simultaneously.
- A pre-action sprinkler system, with the approval of
the FC, may be provided in an area where:
- the nature of the hazard is such that a more rapid
operation than that of a dry-pipe sprinkler system is
required,
- the nature of the hazard is such to require an alarm
or alert signal be transmitted prior to the operation
of the sprinkler system,
- the contents are highly susceptible to water damage,
or
- the sprinkler or sprinkler piping are subject to
mechanical injury.
- Non-fire systems such as energy integrated system may
be connected to a sprinkler system subject to the approval
by the FC.
7.2 Valves
Individual indicating control valves shall be located in readily
accessible locations where a portion of sprinkler systems
protecting areas such as computer rooms, record storage rooms,
cooking equipment and ductwork, rooms intended for hazardous
operations or hazardous substances or other rooms where in
the opinion of the FC there would be a serious water damage
potential.
7.3 Pipes, Fittings and Hangers
- Combustible sprinkler pipes and fittings, such as chlorinated
polyvinyl chloride (CPVC) and polybutylene pipes, are
permitted to be used provided:
- the occupancy is classified as light hazard occupancy
classification,
- the system is a wet pipe sprinkler system,
- the system is located in an area where the ambient
temperature is between 10 C and 50 C,
- horizontal pipes and fittings are protected from
the hazard below by a fixed fire separation having a
fire resistance rating of not less than 15 min. (See
Appendix A),
- vertical pipes and fittings are located in a shaft
and are separated from the remainder of the building
by a fire separation having a fire resistance rating
of not less than 45 min. (See Appendix A),
- pipes and fittings are of a size not exceeding 3½
NPS (nominal pipe size), and
- pipes and fittings are listed and installed in accordance
with the listing requirements of the certification organization.
- Hangers shall not have sharp edges which may come in
contact with combustible piping.
- Hangers spacing and installation methods for combustible
pipes shall be in accordance with the listing requirements
for the pipe.
- Pipes and fittings under air pressure shall not be
buried underground unless the installation is approved
by the FC.
7.4 Sprinklers
- Fast response sprinklers shall be provided in areas
with sleeping facilities and shall be installed in accordance
with the listing requirements of the certification organization.
- Special sprinklers including on-off sprinklers shall
not be used unless specifically permitted by the FC.
7.5 Alarms
- Inside and outside alarm signal devices shall be provided
for the sprinkler system to indicate a water flow condition.
- A water motor gong, where provided, may serve up to
3 sprinkler systems on a common riser.
- Water motor gongs shall be located on an exterior wall
of the building as close to the sprinkler valve as possible,
but not more than 6 m above the valve and with a total
length of pipe not exceeding 20 m.
- Inside alarm signal devices for the sprinkler system
shall be listed and includes electric gong, horn, bell
and siren.
7.6 Testing Facilities
- Facilities shall be provided to test:
- pumping capacity (See Appendix A),
- sprinkler water flow alarms at each floor, and
- pressure regulating equipment serving more than 1
storey in a high building.
7.7 Other Components
- A quick opening device shall be provided for a dry-pipe
valve where:
- the sprinkler system is used for the protection of
an extra hazard occupancy, or
- water takes more than 60 s to reach the test pipe
after the opening of the most remote test pipe valve.
In any case, the delivery of water to the most remote
sprinkler shall not exceed 60 s.
- Where the water supply consists of a connection or
connections from a municipal water service, an excess
pressure pump, manually started and electrically driven,
shall be provided adjacent to the sprinkler alarm valve.
This pump shall be capable of providing a pressure on
the sprinkler system within a period of 30 min. of at
least 175 kPa in excess of the normal maximum municipal
water pressure, measured at the alarm valve. Where there
is more than 1 wet system, at least 1 excess pressure
pump shall be provided for each sprinkler system header.
- The portion of the sprinkler system protecting cooking
equipment and ductwork shall be interlocked with the electrical
power and the fuel supply to the cooking equipment so
as to automatically shut off the electrical power and
fuel supply, including the pilot flames, to all appliances
protected by the system.
|
|
Back
to Fire Sprinkler Standart Main Page |
|
|
|
|
|
|
|