HVAC
Building Control
Fire Safety
Your friend in indoor comfort & safety systems
Home Company Services Case Studies References Agencies Daikin-Vrv Handbook Fires / Hotels AskHvacMan Links Save Energy Contact Us
Fires &
Dictionary
Fire ABCs
Sprinklers
Some Fire Cases
Fire Books
Software
FireBoard
Hotels

Big Hotel Fires

Fire Safety
Detection
Suppression
Hotel Fire Case
Inspection
How to Survive
FireStats
Big Hotel Fires
Hotel Fire Cases
Fire Hazard Classification
Hotel Sprinkler Systems

Hotel Fire News

Special Fires
Hotel Fires
Ship Fires
Industrial Fires
Hospital Fires
Warehouse Fires

Restaurant/Nightclub Discotheque-Fires

High Rise Fires
Airport Fires
Fires
Fires ABC
Big Building Fires
Book About Fires
Fire Stats
Fire Board

Books About Fires

Fire Exit Systems
Software About Fires
Fire Sprinkler Software
Fire Egreess Software
Fire Modelling Software
Sprinkler
What is Fire Sprinkler
Success Stories
Sprinkler Manufacturers
Fire Pump Manufacturers
Standar for Sprinkler Systems
Sprinklered Hotels

Books About Sprinkler

Glossary
Definitions
Manufacturers
Basic
Why
Systems
Public Entry
Recration Areas
 Retail Areas
 Function Spaces
 Guestrooms
Hauskeeping
Elavators
Foods & Beverage
Mechanic Systems
Fire Protection
Kitchen
Site Development
 
Typical Sprinkler Protection for Hotel Guest Rooms

Figure shows typical hotel guestrrom.From entrance lobby there is access to the sleeping room and bath room.Generallay clotghes closet is located in the guest entrance vestibule.

• Sleeping/living :You must use extendend coverage ,quick response sidewall type sprinkler.

• Guestroom Bathrooms: Sprinklers are not required if bathroom is less than 5.10 m2 (55 sq. ft.). (NFPA 13.)Regardless of bathroom area, sprinklers are required when combustible tubs or shower or tub surrounds (plastic / fiberglass) enclosures are used. These means If you have a bathroom with floor area more than 5.1 m2 you must provide sprinklers in bathroom.

• Closets and Pantries: Sprinklers are not required in clothes closets, linen closets and pantries within hotel guestrooms where the area of the space does not exceed 2.2 m2 (24 sq. ft.). Closets and pantries with washer, dryer, water heater, mechanical or electrical equipment require sprinklers.

Not:Guestroom sidewall sprinklers distance to ceiling subject to sprinkler listing.You must use particular sprinkler manufacturer design criteria.

You can select your sprinkler type from here

Back

 
 
 
  http://www.iklimnet.com
 
Air Grilles
Air Diffusers
Air Quailty
All Air Systems
All Water Systems
Boilers
Building .Managament Systems ..BMS
Burners
Chillers
Cooling Towers
Cooling Load Calculation
Cryogenics
Energy Saving
Duct
Duct ,Smacna
Dampers ,Air
Dust Collection
Fans
Fire Dampers
Glass Selection
Heating
Heat Exchangers,water
Heat Recovery
Heat Tracing Systems
Hepa Filters
Hvac Applications
Humidifiers / Dehumidifiers
Insulation , Duct
Insulation , Pipe
Insulation , Sound
Nano Tech.,In Building
Occupancy Sensors
Pneumatic Conveying
Piping
Pool Ventilation
Process Piping
Psychrometry
Pumps
Radiant Heating
Refrigerant Systems
Solar Collectors
Sound
Steam Generation
Tables & Charts Gnr.
VAV Sytems
Valves
Ventilation
VRV Systems