CONSTRUCTION - STRUCTURAL ASSEMBLIES 3.
(1) A hotel or an addition to a hotel constructed after
the 1st day of September, 1971 that is one storey in height
"shall have,
(a) floor assemblies above basements
constructed as fire separations of heavy timber construction,
3/4-hour fire separations or combinations thereof; and
(b) load bearing walls, columns and
arches supporting floor assemblies above basements constructed
of heavy timber construction, construction having a 3/4-hour
fire resistance rating or combinations thereof.
(2) A hotel or an addition to a hotel constructed
after the 1st day of September, 1971 that is two storeys
in height shall have,
(a) floor assemblies constructed as
fire separations of heavy timber construction, 3/4-hour
fire separations or combinations thereof;
(b) balconies and mezzanines constructed
of heavy timber construction, noncombustible construction,
construction having a 3/4-hour fire resistance rating or
combinations thereof; and
(c) load bearing walls, columns and
arches constructed of heavy timber construction, construction
having 3/4-hour fire resistance rating or combinations thereof.
(3) A hotel or an addition to a hotel that is constructed
after the 1st day of September, 1971 that is three or more
storeys in height shall be of noncombustible construction
and shall have,
(a) floor assemblies constructed as
two hour fire separations;
(b) a roof assembly, balconies and
mezzanines of construction having a one hour fire resistance
rating; and
(c) load bearing walls, columns and
arches having a fire resistance rating at least equivalent
to the fire resistance rating of the construction which
they support.
(4) Despite subsections (1), (2) and (3),
(a) a floor assembly is not required
to be constructed as a fire separation between the first
storey and the next storey above, between the first storey
and the first basement below or between two contiguous basements
or storeys up to the fifth storey if,
(i) the hotel is of noncombustible construction,
(ii) the unseparated floors do not have sleeping accommodation,
and
(iii) the required fire resistance rating of the floor assembly
is maintained;
(b) storage garages and open air parking
garages are not required to have a separation between floors;
and
(c) where alternative measures can
be demonstrated that, in the opinion of the Fire Marshal,
provide an equivalent level of safety, the Fire Marshal
may approve the measures and may modify or waive the fire
resistance rating or fire separation of construction assemblies
required by subsections (1), (2) and (3).
FIRE WALLS
4. (1) Unless otherwise approved, where the basic
area of a hotel or of an addition or additions constructed
after the 1st day of September, 1971 is more than 600m2
and the hotel or the addition or additions are not of noncombustible
construction, the hotel or addition or additions shall be
divided by fire walls or by fire walls and exterior walls
into vertical compartments having a basic area of not more
than 600m2.
(2) Where an addition or additions having a basic
area of more than 600m2 are made to a hotel after
the 1st day of September, 1971 and the addition or additions
or the original hotel are not of noncombustible construction,
a fire wall shall be erected between the part of the hotel
existing on the 1st day of September, 1971 and the addition
or additions, unless otherwise approved.
(3) Where a hotel or an addition to a hotel constructed
or a building converted for hotel use after the 1st day
of September, 1971 is directly connected to an adjacent
building which is not a hotel, the hotel shall be separated
from the adjacent building by a fire wall or another approved
means or the adjacent building shall meet the requirements
of this Regulation as if it were a hotel.
(4) Subsidiary occupancies such as assembly rooms,
licensed or unlicensed lounges, dining rooms, cafeterias,
hairdressing and barber shops and banks that are operated
in connection with a hotel shall be separated from the hotel
by at least a one hour fire separation unless they are protected
by a fully automatic sprinkler system.
STAIRWAYS
5. (1) Interior stairways connecting basements,
storeys or the first storey and the first basement below
shall be separated from the hotel by a 3/4-hour fire separation,
unless otherwise approved.
(2) Despite subsection (1), a stairway in a hotel
connecting only the first storey and the next storey above,
the first storey and the first basement below, two contiguous
basements or two contiguous storeys up to the fifth storey
need not be separated, provided,
(a) the hotel is of noncombustible
construction; and
(b) the unseparated floors do not have
sleeping accommodation.
(3) Unless otherwise approved, exterior stairways
or fire escapes sewing any storey above the second storey
or any basement below the first basement in a hotel shall
be separated from the hotel,
(a) by a 3/4-hour fire separation;
or
(b) by having all,
(i) windows, except first
storey display windows, protected by wired glass in fixed
steel or steel-clad sash,
(ii) doorways protected
by fire doors, and
(iii) other openings protected
by closures,
where the windows, doorways or other openings are
located horizontally within 3m of the stairway, within 3
storeys or 10m below it or within 1.8m above it.
(4) Exterior stairways or fire escapes of a hotel
shall be,
(a) constructed in a strong substantial
manner of metal or concrete; and
(b) securely fixed to the hotel,
but an exterior stairway extending only up to the
second storey of a hotel that is not or is not required
to be of noncombustible construction may be constructed
of wood if,
(c) all posts or brackets are at least
89mm in their least nominal dimension; and
(d) all other woodwork is at least
38mm in its least nominal dimension.
(5) Exterior stairways leading across roofs shall
be provided with handrails on both sides of the walkway
leading to the stairway at the edge of the roof, unless
otherwise approved.
(6) Exterior stairways or fire escapes below grade
shall be,
(a) enclosed by side walls and a roof,
with a door to ground at the upper landing;
(b) provided with a roof projecting
horizontally for a distance of at least 1.8m beyond any
step or landing; or
(c) provided with some other approved
construction or device to prevent snow accumulating in the
stairway.
6. Where a stairway in a hotel or an addition to
a hotel constructed after the 1st day of September, 1971
is required as an exit to ground from a basement or storey
and is required to be separated, the separation shall be
constructed with an exterior exit so that a person on the
stairway will be able to reach the outside without having
to leave the separation and re-enter the hotel.
SLEEPING ACCOMMODATION
7. (1) Hotel suites and sleeping rooms occupied
individually in a hotel or an addition to a hotel constructed
after the 1st day of September, 1971 shall be separated
from adjacent rooms, suites and corridors or other interior
exits by a 3/4-hour fire separation.
(2) Despite subsection (1), the 3/4-hour fire separation
requirement does not apply to doorway openings.
8. (1) The door of a sleeping room occupied individually
and the door of a suite opening into a sleeping room occupied
individually, another suite or a corridor or other interior
exit, in a hotel or an addition to a hotel constructed after
the 1st day of September, 1971, shall be of solid wood core
construction with a thickness of 44.5mm, unless otherwise
approved.
(2) The door of a sleeping room occupied individually
and the door of a suite opening into a corridor or other
interior exit shall not be,
(a) undercut more than 19mm; or
(b) equipped with grills or other openings.
(3) No transom, grill or other ventilation opening
that is not connected to a duct in an air handling system
shall be installed between the floor and the ceiling in
a wall separating a corridor or other interior exit from
a sleeping room occupied individually or from a suite.
(4) Subsection (3) does not apply to a transom,
grill or other ventilation opening installed between the
floor and the ceiling in a wall separating a corridor or
other interior exit from a sleeping room occupied individually
or from a suite where the transom, grill or other ventilation
opening,
(a) was installed before the 1st day
of September, 1971; and
(b) is provided with a fire separation
at least equal to the fire separation of the door of the
sleeping room or suite opening onto the corridor or other
interior exit.
HAZARDOUS AREAS
9. (1) Boilers, furnaces, incinerators and fuel-fired
space heating appliances shall be separated from the hotel
by a one hour fire separation unless otherwise approved.
(2) Despite subsection (1),
(a) an oil or gas fired heating appliance
may be installed on the roof of a hotel of noncombustible
construction;
(b) a sealed combustion chamber, oil
or gas fired heating appliance may be installed in any room
that is separated from the hotel by a 3/4-hour fire separation
or by walls and ceilings of plaster, plasterboard or other
approved noncombustible material, provided the room has
direct access to the outdoors; and
(c) a fireplace or lamp need not be
separated.
(3) Laundry rooms, storage areas exceeding .6m2
in floor area and maintenance shops shall be separated from
the hotel by at least a 3/4-hour fire separation, unless
otherwise approved.
(4) Solid core wood doors at least 44.5mm thick
are acceptable as fire doors for closures on openings requiring
protection under subsection (3).
10. (1) A kitchen or a room containing a fuel-fired
cooking appliance in a fixed location shall be separated
from the hotel by a 3/4-hour fire separation, unless otherwise
approved.
(2) Despite subsection (1), a kitchen,
(a) within a suite need not be separated;
or
(b) provided with cooking equipment
having an approved exhaust system and fixed extinguishing
system need not be separated.
(3) Where a kitchen is connected to an adjacent
dining area by means of a pass-through opening,
(a) the kitchen and the dining area
shall be separated from the hotel as an integral area; or
(b) the kitchen shall be separated
from the dining area and the pass-through opening shall
be protected by a shutter, closeable on the operation of
a fusible link or some other approved device.
11. (1) Linen and rubbish chutes shall be enclosed
in shafts or separated from the hotel in another approved
manner to provide at least one hour fire separation.
(2) In hotels and additions to hotels constructed
after the 1st day of September, 1971,
(a) linen chute and rubbish chute service
openings in chutes enclosed in shafts shall be protected
by approved chute doors listed by Underwriters' Laboratories
of Canada or by another approved testing laboratory;
(b) linen chute and rubbish chute doors
in chutes enclosed in shafts shall open into rooms which
are separated from the hotel by a 3/4-hour fire separation;
and
(c) linen chutes and rubbish chutes
enclosed in shafts shall be equipped at the top with an
opening or other approved device for automatic venting to
the outside.
(3) Linen chutes and rubbish chutes enclosed in
shafts shall terminate or discharge directly into rooms
which are separated from the hotel by a one hour fire separation.
(4) An automatic sprinkler system shall be installed
in a linen or rubbish chute extending three or more storeys,
so that there is sprinkler head protection at the top of
the chute and in the linen or rubbish room at the bottom
of the chute. |