FIRE PROTECTION DUTIES of HOTELKEEPER
DISCOVERY OF FIRE
55. When a fire is discovered in a hotel, the manager
or the person in charge shall immediately,
(a) ensure that the fire alarm signal is
sounded; and
(b) where the hotel is in a municipality
that has a fire department, ensure that the fire department
is called.
56. No person shall silence a fire alarm signal in a
hotel unless it has been determined that there is no fire
or that the fire has been extinguished.
PERSON IN CHARGE
57. In a hotel, a manager, guard or other person in
charge shall be,
(a) available on the premises at all times;
and
(b) on duty on the premises at all times,
if the hotel is four or more storeys in height or has a
total floor area of 4,000m2 or more.
EVACUATION
58. An approved fire safety plan shall be posted in
the main reception area and in all other locations required
by the inspector and shall indicate,
(a) the method of sounding an alarm;
(b) the procedure of the evacuation plan;
(c) the use of fire fighting equipment;
(d) the control of fire hazards;
(e) the use of voice communication systems
where provided;
(f) the procedures for control of elevators;
(g) the procedure for initiating smoke control
or fire emergency systems where provided;
(h) a procedure to ensure fire department
access to the building; and
(i) the location of building facilities
provided for the safety of occupants from fire.
59. (1) A notice shall be displayed on the inside of
the exit door of each suite and each room occupied individually
and shall indicate,
(a) the action to be taken by guests discovering
a fire or hearing a fire alarm signal;
(b) the fire safety rules of the hotel and,
where the inspector so requires, the location of exits.
(2) In a high-rise hotel, a record including schematic
diagrams of the fire emergency systems shall be maintained
at a central alarm and control facility, and the record
shall include instructions to the supervisory staff and
fire department for the operation of fire protection systems.
(3) A copy of a list of fire emergency procedures and
other duties of supervisory staff shall be given to all
supervisory staff members.
(4) At least one copy of such parts of the fire safety
plan as the inspector requires shall be prominently posted
and maintained on each floor area.
(5) Specific fire safety and fire emergency instructions
for staff in work areas shall be posted in each work area.
TRAINING
60. (1) The hotelkeeper shall ensure that hotel employees
are familiar with,
(a) the method of sounding a fire alarm;
(b) evacuation procedures;
(c) the use of fire fighting equipment,
including portable fire extinguishers and standpipe and
hose systems;
(d) methods of controlling fire hazards
in the hotel;
(e) the location of building facilities
provided for the safety of occupants;
(f) in high-rise hotels, the use of the
voice communication systems;
(g) procedures for the use of elevators
and the evacuation of non-ambulatory occupants;
(h) the action to be taken in initiating
any smoke control or fire emergency systems before the arrival
of firefighters; and
(i) procedures established to facilitate
fire department access to the building and to the location
of any fire.
(2) The hotelkeeper shall ensure that a fire drill for
all hotel employees is conducted at least once during every
twelve month period.
(3) In high-rise hotels, the hotelkeeper shall ensure
that a fire drill for supervisory staff and hotel staff
assigned special duties in the event of fire is conducted
at least once during every three month period.
FIRE ALARM AND VOICE COMMUNICATION SYSTEMS
61. (1) The hotelkeeper shall ensure that the fire alarm
system, smoke alarms and, where it is required, the voice
communication system,
(a) are operational at all times; and
(b) are tested, inspected and maintained
in accordance with U.L.C. S536-1979 Standard for the testing,
inspection and maintenance of existing fire alarm systems.
(2) Every fire alarm system and voice communication
system shall be tested in the presence of an inspector at
least once a year.
(3) A record indicating the date and time of all tests
under subsections (1) and (2) and the name of any inspector
present shall be kept on the premises.
(4) The hotelkeeper shall ensure that where a fire alarm
system or voice communication system or any part thereof
is shut down, alternate measures acceptable to the inspector
are established to maintain the safety of building occupants.
(5) Where a central alarm and control facility is provided
in a hotel, the hotelkeeper shall ensure that,
(a) a daily check of the central alarm and
control facility is carried out to ensure no trouble is
indicated in the system; and
(b) the voice communication system between
the floor areas and the central alarm and control facility,
and loudspeakers operated from the central alarm and control
facility, are tested monthly and yearly as required under
clause (1)(b).
62. (1) The hotelkeeper shall ensure that the standpipe
and hose system is regularly inspected and maintained and
is ready for operation at all times.
(2) The hotelkeeper shall ensure that,
(a) the plugs or caps of the fire department
connection are removed annually, the threads inspected for
wear, rust or obstructions and the plugs or caps re-secured
and wrenched tight;
(b) whenever a standpipe and hose system
or part of the system is shut down, the fire department
is notified;
(c) hose cabinets are inspected monthly
to verify that the hose is in proper position and that all
the equipment is in place and in operable condition;
(d) standpipe and hose system equipment
is used for fire protection only;
(e) standpipe hose cabinets are conspicuously
identified and unobstructed;
(f) hose valves are inspected annually to
ensure that they can be operated by hand and that there
is no water leakage into the hose;
(g) the fire department connection is marked
in a manner acceptable to the inspector, indicating its
intended service and size;
(h) standpipe hose are removed and re-racked
annually and after use and any worn gaskets in the couplings
at the hose valve and at the nozzle are replaced;
(i) each hose connection in a dry standpipe
system is provided with a legible waterproof sign reading
"DRY STANDPIPE FOR FIRE DEPARTMENT USE ONLY";
(j) all valves controlling water supplies
to the standpipe and hose system are locked or sealed in
the "OPEN" position;
(k) flow and pressure tests are conducted
annually at the highest and most remote hose valve or hose
connection to verify that the water supply for standpipes
is provided as originally designed;
(l) standpipe system piping which normally
remains dry is hydrostatically tested at least once every
five years at a pressure of at least 1,400 kPa for two hours,
or where the normal hydrostatic pressure exceeds 1,050 kPa,
at 350 kPa more than the normal hydrostatic pressure;
(m) a record of inspections, testing and
maintenance of the standpipe and hose system is kept on
the premises; and
(n) standpipe systems that have been modified
or extended or are to be restored to service after a period
of disuse exceeding one year are hydrostatically tested
at a pressure of at least 1,400 kPa for two hours, or where
the normal hydrostatic pressure exceeds 1,050 kPa, at 350
kPa more than the normal hydrostatic pressure.
SPRINKLER SYSTEMS
63. (1) In the event of fire, the hotelkeeper shall
ensure that the sprinkler control valves are not closed
until the fire is extinguished or is considered to be under
control by other means, as determined by the fire department.
(2) The hotelkeeper shall ensure that the sprinkler
system is repaired and maintained and that repair and replacement,
alterations of sprinkler system components and tests following
alterations and repairs are in accordance with NFPA 13-1980
"Sprinkler Systems".
(3) The hotelkeeper shall ensure that,
(a) no obstructions such as partitions,
racks or piled stock are placed so as to interfere with
the effectiveness of water discharge from sprinklers;
(b) whenever the automatic sprinkler system
or a part of the system is shut down, the fire department
is notified and alternate acceptable measures satisfactory
to the inspector are undertaken;
(c) all valves controlling water supplies
to sprinkler and alarm connections, except electrically
supervised valves, are checked weekly to ensure that they
are in the open position;
(d) the sprinkler system piping is not used
to support anything;
(e) exposed sprinkler pipe hangers are checked
yearly to ensure that they are in good repair;
(f) air pressure on dry pipe systems is
checked weekly to ensure that the system is maintained at
the required operating pressure;
(g) dry pipe valve rooms or enclosures in
unheated buildings are checked as often as necessary during
periods of freezing weather to ensure that adequate temperature
is maintained to prevent freezing;
(h) sprinkler heads are checked at least
once yearly to ensure that they are free from damage, corrosion,
grease, dust, paint or whitewash, and replaced where necessary
as a result of such conditions;
(i) auxiliary drains are inspected during
cold weather to prevent freezing;
(j) at least once in every fifteen year
period, the dry pipe systems are inspected for obstructions
in the sprinkler piping and, if necessary, the entire system
flushed of foreign material;
(k) the priming water supply for dry pipe
systems is inspected annually to ensure that the proper
level above the dry pipe valve is maintained;
(l) plugs and caps on fire department connections
are removed annually, the threads inspected for wear, rust,
or obstruction, and the plugs or caps re-secured and wrenched
tight; and
(m) the fire department connection is marked
in a manner acceptable to the inspector, indicating its
intended service and size.
(4) The hotelkeeper shall ensure that,
(a) notice of an intended test of water
flow or other test of the sprinkler system is given to all
parties who could be affected by an alarm, including the
fire department;
(b) alarms on all sprinkler systems are
tested monthly, using the alarm test connection located
at the sprinkler valve;
(c) water flow alarms are tested on wet
sprinkler systems annually, using the most hydraulically
remote test connection;
(d) dry pipe valves are tripped annually
by means of the system test pipe to ensure that they operate
satisfactorily and that the sprinkler alarms are in operating
condition;
(e) sprinkler system water pressure is tested,
annually and after any sprinkler system control valve has
been operated, with the main drain valve fully open, to
ensure that there are no obstructions or deteriorations
of the main water supply; and
(f) where an electrical supervisory signal
service is provided for a sprinkler system,
(i) all transmitter and water
flow activated devices are tested at intervals of not more
than two months, and
(ii) gate valve supervisory
switches, tank water level devices, building and tank water
temperature supervisory devices and other sprinkler system
supervisory devices are tested at intervals of not more
than six months.
WATER SUPPLIES FOR FIRE PROTECTION
64. (1) The hotelkeeper shall ensure that,
(a) valves controlling water supplies exclusively
for fire protection are inspected weekly to ensure that
they are wide open and that they are sealed or locked in
that position;
(b) all tanks for fire protection, tanks
supporting structures and water supply systems, including
piping, control valves, check valves, heating systems, mercury
gauges and expansion joints are inspected annually to ensure
that they are in satisfactory operating condition; and
(c) water levels in gravity tanks are inspected
monthly to ensure that the proper level is maintained.
(2) The hotelkeeper shall ensure that,
(a) fire pumps are tested monthly at rated
speed and the fire pump discharge pressure, suction pressure,
lubricating oil level, operative condition of relief valves,
priming water level and general operating conditions are
inspected;
(b) fire pumps are tested annually at full
rate capacity to ensure that they are capable of delivering
the rated flow; and
(c) records are kept of all fire pump tests,
including flow tests, and made available to the inspector
upon request.
PORTABLE EXTINGUISHERS
65. Portable fire extinguishers shall be,
(a) conspicuously located;
(b) readily accessible in the event of fire;
(c) set on hangers, shelves or brackets,
in a manner acceptable to the inspector; and
(d) installed so that the top of the extinguisher
is not more than,
(i) 1.1m above the floor, where
the gross weight of the extinguisher is more than 18kg,
or
(ii) 1.5m above the floor, where
the gross weight of the extinguisher is 18kg or less.
66. The hotelkeeper shall ensure that,
(a) portable fire extinguishers are inspected
monthly;
(b) defective portable fire extinguishers
are repaired, replaced or recharged as necessary;
(c) portable fire extinguishers are maintained
in accordance with the recommendations of the manufacturers;
(d) each portable fire extinguisher has
a tag securely attached to it, showing the maintenance or
recharge date, the servicing agency and the signature of
the person who performed the service;
(e) a permanent record of the inspection
and maintenance of all portable fire extinguishers, including
the maintenance date, the examiner's name, and a description
of any maintenance work or hydrostatic testing carried out,
is kept on the premises;
(f) after use, portable fire extinguishers
are replaced and recharged according to the instructions
given on the extinguisher's nameplate;
(g) extinguisher shells, cartridges or cylinders
that rupture or show leakage or permanent distortion in
excess of specified limits are removed from service;
(h) all portable fire extinguishers are
subjected to hydrostatic testing at the intervals and test
pressures indicated on the extinguisher's nameplate; and
(i) a label is fixed to every portable fire
extinguisher after hydrostatic testing indicating the month
and year the test was performed, the test pressure used
and the name of the person or agency performing the test.
67. No vaporizing liquid fire extinguisher shall be
installed in a hotel, unless approved.
FIRE HAZARDS
68. (1) Every hotel shall be kept clean and free of
rubbish and other debris.
(2) Combustible materials shall not be permitted to
accumulate in any part of an elevator shaft, ventilating
shaft, stairway, fire escape or other means of egress in
a hotel.
(3) The contents of containers for waste, rubbish and
other debris shall be removed from the hotel at least once
a week.
(4) Combustible materials shall not be used to absorb
flammable or combustible liquid spills.
(5) Greasy and oily rags or materials subject to spontaneous
heating shall be deposited in a receptacle constructed of
noncombustible materials having a melting point of not less
than 650°C, designed without any openings in the side and
bottom and provided with a self-closing, tightly fitted
cover.
(6) Lint traps in laundry equipment in a hotel shall
be cleaned regularly to prevent excessive accumulation of
lint.
(7) All ashes shall be stored in receptacles constructed
of non-combustible materials having a melting point of not
less than 650°C, designed without any openings in the side
and bottom and provided with a self-closing tight fitting
cover.
(8) Combustible materials shall not be stored in the
same container with ashes.
(9) Storage containers for ashes shall not be placed
within 1m, measured from the sides and top, of combustible
materials and shall not be placed on combustible floor surfaces
unless they are equipped with flanged bottoms or legs at
least 50mm in height.
(10) Where conditions are such as to make smoking a
fire or explosion hazard in a hotel, smoking shall be permitted
only in specifically approved smoking areas.
(11) The areas where smoking is not permitted shall
be identified by,
(a) signs having lettering 50mm high with
a 12.5mm stroke;
(b) symbols with dimensions of 150 x 150mm;
or
(c) instructions established under a fire
safety plan and available to all persons.
(12) Flammable liquids shall not be used for cleaning
purposes in a hotel.
(13) Flammable gases shall not be used to inflate balloons
in a hotel.
69. Containers constructed of noncombustible material
and having self-closing covers shall be provided in public
washrooms, and in other locations where they may be required
throughout a hotel, for the deposit of used paper towels,
rubbish and other debris.
FIRE SEPARATIONS
70. The hotelkeeper shall ensure that,
(a) where fire separations between major
occupancies, fire walls or fire separations between rooms,
corridors, shafts and other spaces or closures in fire separations
are damaged so as to affect their fire resistance rating,
the damage shall be repaired so that the integrity of the
fire separation, wall or closure is restored;
(b) defects that interfere with the operation
of closures in fire separations are corrected;
(c) closures are maintained, to ensure that
they are operable at all times, by,
(i) keeping fusible links and
heat or smoke activated devices undamaged and free of paint
and dirt,
(ii) keeping guides, bearings
and stayrolls clean and lubricated,
(iii) inspecting door hardware
and other ancillary components regularly and making necessary
adjustments or repairs to ensure proper closing and latching,
and
(iv) repairing or replacing
inoperative parts of hold-open devices and automatic releasing
devices whenever necessary;
(d) closures in fire separations are not
blocked or wedged open; (e) doors in fire separations are
inspected monthly;
(f) doors in fire separations are checked
as frequently as is necessary to ensure that they remain
closed, unless equipment is installed to close the door
automatically;
(g) fire dampers and fire-stopped flaps
are inspected annually or on an approved schedule; and
(h) door openings and the surrounding areas
are kept clear of anything that would be likely to obstruct
or interfere with the fire separation of the door.
DRAPES, CURTAINS AND DECORATIVE MATERIALS
71. No drapery, curtain or other decorative textile,
foam or other material shall be placed in a place of assembly,
or in a lobby, corridor, stairway, or other exit, unless
it is,
(a) noncombustible; or
(b) treated with a fire-retardant at least
once a year, or in accordance with the manufacturer's instructions,
whichever is oftener.
OPEN FLAMES -- s. 72
72. (1) Unless approved, open flames shall not be permitted
in a hotel in such quantities and in such a manner as to
a create a fire hazard.
(2) Decorative and lighting devices having open flames
may not be used unless they are,
(a) approved;
(b) securely supported in noncombustible
holders; and
(c) so located and protected that combustible
materials will not come in contact with or be ignited by
the flames.
(3) In places of public assembly, flaming meals or drinks
shall be ignited only at the table where they are served
to diners.
(4) A portable fire extinguisher complying with sections
44 and 45 and rated as 1A, 5-B,C or higher shall be available
wherever refuelling of appliances and containers used for
flaming meals or drinks takes place and on every serving
cart or table where flaming meals and drinks are being served.
(5) No appliance or container used for igniting flaming
meals or drinks shall be refuelled in a dining area.
RUGS AND CARPETS
73. Every rug, carpet or other floor covering in a place
of assembly or in a lobby, corridor, stairway or other exit
in a hotel shall be maintained so that it does not crease,
wrinkle or otherwise impede egress.
EXITS
74. (1) All exit doors shall be clearly identified,
and no draperies, mirrors or decorations shall be placed
on or over exit doors.
(2) No lock, padlock, bar, chain or other device that
prevents, or is intended to prevent, the free use of the
door for exit purposes shall be installed or maintained
on or in connection with an exit door.
(3) Exit doors, corridors, aisles and other means of
egress shall be maintained free of obstruction.
(4) No furniture shall be placed in a corridor that
serves a floor area that has sleeping accommodation, except
as approved.
(5) Exterior passageways and exterior exit stairs shall
be maintained free of snow and ice accumulations.
(6) Where equipment is provided to melt snow or ice
on exterior passageways and exterior exit stairs in a hotel,
the equipment shall be maintained in working order.
(7) All required exit signs shall be clearly visible
and maintained in a clean and legible condition.
(8) Internally illuminated exit lights shall be clearly
illuminated whenever the building is occupied.
(9) Emergency lighting unit equipment shall be maintained
in accordance with the manufacturer's recommendations.
NUMBER OF PERSONS
75. (1) The occupant load of a place of assembly determined
under section 13 shall not be exceeded at any time.
(2) The occupant load of a place of assembly shall be
posted in the place of assembly in a manner acceptable to
an inspector.
ROWS OF MOVABLE SEATS
76. (1) Every exit from a place of assembly that contains
rows of movable seats shall be accessible from any row by
aisles.
(2) No centre seating section in a place of assembly
that contains rows of movable seats shall have more than
sixteen seats in a row and no seating section running to
a side wall shall have more than eight seats in a row.
(3) Where an exit is located at the side of a place
of assembly that contains rows of movable seats, a cross
aisle that affords access to the exit shall be provided.
(4) An aisle in a place of assembly that contains rows
of movable seats shall be at least 1.1m wide.
(5) No person shall stand in an aisle or place additional
seats, chairs or tables in a place of assembly so as to
reduce the aisle space required by this section.
(6) Unless otherwise approved, where the occupant load
exceeds 200 persons in an assembly area containing movable
seats,
(a) the aisles shall be at least 1.65m wide;
and
(b) not more than one person for every 1.2m2
of floor area shall be permitted in the assembly area.
HIGH-RISE FIRE PROTECTION
77. (1) The hotelkeeper of a high-rise hotel shall ensure
that the required emergency systems are properly maintained
and operative at all times.
(2) The hotelkeeper of a high-rise hotel shall ensure
that,
(a) keys required to recall elevators and
to permit independent operation of each elevator are kept
in a suitably identified box in a conspicuous location on
the outside of the elevator shaft and at the central alarm
and control facility;
(b) an elevator designed for firefighters'
use is maintained in operable condition and is identified
on the floor containing the central alarm and control facility
and at any interchange level;
(c) access to windows and panels required
to vent floor areas and to manually operable vents to vestibules
is unobstructed;
(d) windows and panels provided for venting
floor areas can be opened readily without the use of keys;
and
(e) manually operable vents to vestibules
are maintained in an operable condition.
(3) The hotelkeeper of a high-rise hotel shall ensure
that, at intervals of not more than three months,
(a) every elevator door opening device operated
by means of photoelectric cells is tested to ensure that
the device becomes inoperative after the door has been held
open for more than ten seconds with the photoelectric cell
covered;
(b) key operated switches located outside
an elevator shaft are tested to ensure that actuation of
the switch will render the emergency stop switch in each
car inoperative and bring all cars to the street floor or
transfer lobby by cancelling all other calls after the car
has stopped at the next floor at which it can make a normal
stop; and
(c) key operators' switches in each elevator
car are tested to ensure that actuation of the switch will,
(i) enable the elevator to operate
independently of other elevators,
(ii) allow operation of the
elevator without interference from floor call buttons,
(iii) render door protective
devices inoperative, and
(iv) permit the opening of power-operated
doors only by continuous pressure on the door opening buttons
or switches, so that if the "open" button or switch is released
while the door is opening, the door will automatically close.
(4) The hotelkeeper of a high-rise hotel shall ensure
that,
(a) closures in vent openings into the smoke
shafts from each floor area are inspected at least once
in each five year period;
(b) every closure in an opening to the outdoors
at the top of a smoke shaft is inspected annually to ensure
that it will open,
(i) manually from outside the
building,
(ii) on a signal from a smoke
or heat actuated device in the smoke shaft, and
(iii) when a closure in an opening
between a floor area and the smoke shaft opens;
(c) all elevators in an elevator shaft that
is intended for use as a smoke shaft are inspected semi-annually,
to ensure that on activation of the fire alarm system they
will return to the street floor and remain inoperative;
and
(d) controls for air-handling systems used
for venting in the event of a fire are inspected annually,
to ensure that air is exhausted from each floor area to
the outdoors as required.
(5) The hotelkeeper of a high-rise hotel shall ensure
that,
(a) the smoke control equipment is maintained
to ensure satisfactory operation;
(b) where smoke control measures contained
in the ACNBC publication "Measures for Fire Safety in High
Buildings" are used, inspections and tests are conducted
as outlined in section 7.3 of the National Fire Code of
Canada, 1985; and
(c) where smoke control systems are designed
to meet the requirements of sentences 3.2.6.2(2), (3) and
(4) of the Ontario Building Code, inspection and testing
of the equipment shall be in accordance with procedures
established by the designer of the system.
TESTS AND RECORDS
78. (1) Where tests, repairs or alterations are made
to fire protection installations, including sprinkler and
standpipe systems, the hotelkeeper shall notify the fire
department and the building occupants where necessary for
safety in the event of a fire emergency.
(2) The hotelkeeper shall keep a written record of all
tests and corrective measures for a period of two years
after they are made and shall make the record available
upon request of the inspector.
HEATING, VENTILATION AND AIRCONDITIONING
79. The hotelkeeper shall ensure that,
(a) every defective heating appliance in
a hotel is removed, repaired or replaced when it creates
a hazardous condition;
(b) chimneys and chimney liners that constitute
a fire hazard are repaired or replaced as necessary;
(c) coal and wood bins are located at least
1.2m from any heating appliance;
(d) hoods, filters and ducts subject to
the accumulation of combustible deposits are checked weekly
and are cleaned when the deposits create a fire hazard;
(e) every chimney, flue and flue pipe is
inspected annually and cleaned as often as may be necessary
to keep it free of accumulations of combustible deposits;
(f) where flue pipes are removed, every
flue pipe hole is closed with a tight fitting noncombustible
cover, compatible with the chimney flue construction;
(g) chimneys, flue pipes and breaching are
maintained in a safe operating condition;
(h) except within bedrooms and suites, disconnect
switches for mechanical airconditioning and ventilation
systems are inspected annually to establish that the system
can be shut down;
(i) ventilation shafts in hotels are used
only for ventilating purposes;
(j) work on ducts involving the use of heat-producing
devices for cutting, welding or soldering, is not undertaken
before the ventilation system has been shut down, the duct
cleaned of any accumulations of combustible deposits and
any combustible lining and covering materials that could
be ignited by the work have been removed;
(k) commercial cooking equipment exhaust
and fire protection systems are maintained in accordance
with the manufacturer's recommendations;
(l) instructions for manually operating
fire extinguishing installations are posted conspicuously
in the kitchen as part of the fire safety plan; and
(m) solid fuel burning appliances and equipment
are installed and maintained in accordance with the manufacturer's
recommendations.
EMERGENCY POWER SUPPLIES
80. The hotelkeeper shall ensure that,
(a) the emergency power supply system is
inspected, tested and maintained in accordance with CSA
C282-1977--"Emergency Electrical Power Supply for Building";
(b) where an emergency power system or any
part of it is shut down, alternate safety measures acceptable
to the inspector are undertaken;
(c) where an emergency power supply is installed,
instructions are provided for switching on essential loads
and for starting a generator where this is not done automatically;
(d) a written record of inspections, performance,
test periods and repairs is kept as required by CSA C282-1977;
(e) the amount of fuel stored and connected
to the emergency power system is sufficient to operate the
engine for eight hours; and
(f) the liquid fuel storage tanks for emergency
power supplies are drained and refilled with a fresh supply
of fuel at least once a year, unless otherwise approved.
SPECIAL EXTINGUISHING SYSTEMS
81. The hotelkeeper shall ensure that,
(a) except where this section provides otherwise,
inspection and maintenance of special extinguishing systems
is carried out in accordance with the manufacturer's recommendations;
(b) where a special extinguishing system
or any part of it is shut down, alternate safety measures
acceptable to the inspector are established;
(c) written records are kept of all periodic
inspection, maintenance and testing;
(d) operating and maintenance instructions
are posted near the equipment and near manual controls,
if any;
(e) valves and controls are clearly marked
to indicate their function and are accessible at all times;
(f) extinguishing agent containers provided
for special extinguishing systems are fully charged with
the proper quantity of extinguishing agent and the necessary
operating pressure is maintained;
(g) discharge outlets for special extinguishing
systems are kept free of dirt and residue;
(h) piping and equipment is mechanically
secure and accessible for cleaning and maintenance; and
(i) no replacement equipment and devices
provided for special extinguishing systems are used unless
they are suitable for the installation in which they are
placed.
|