DEFINITIONS
1. (1) In this Regulation,
"air handling system" means an assembly of connected
ducts, plenums or other air passages with associated fittings
through which air is conducted, but does not include a cooking
exhaust system;
"approved" means approved by the Fire Marshal;
"basement" means that portion of a hotel between two
floor levels that is situated below the first storey;
"basic area" means the horizontal projected area inside
the perimeter of the exterior or boundary walls;
"dead-end corridor" means a corridor or part of a corridor
from which an exit is accessible in one direction only;
"exit" includes,
(a) an aisle, doorway, corridor, hallway,
passageway, stairway, ramp, lobby, foyer and vestibule,
but does not include,
(b) an escalator, elevator, slide escape,
sliding door, turnstile, revolving door, overhead door, folding
door, doorway to an enclosed court, ladder, hatch or window, except
where approved as an alternate means of egress from a boiler,
furnace, mechanical service, electrical service or other service
room, or
(c) a ramp with a gradient in excess of one
in eight, or a doorway or passageway leading the public through
a boiler room, furnace room, kitchen or other service room;
"fire alarm signal" means a clearly audible alarm or
sound that is intended to warn of fire;
"fire alarm signalling device" means a sounding device
that emits a fire alarm signal;
"fire damper" means a blade or damper arranged to interrupt
air flow through part of an air handling system, so as to restrict
the passage of heat and smoke;
"fire door" means a solid steel or hollow-steel or steel-clad
door and frame or combination thereof or other approved door and
frame that is self-closing and positive latching and may contain
wired glass panels;
"fire extinguisher rating" means the rating of an extinguisher
for extinguishing capacity and class of fire;
"fire hazard classification" means the rating assigned
to a material upon an approved test of the flame spread, fuel
contribution and smoke development of a representative specimen
conducted by,
(a) The National Research Council of Canada,
(b) Underwriters' Laboratories of Canada,
or
(c) another approved testing laboratory;
"fire resistance rating" means the rating assigned to
an assembly upon an approved test of the time of fire resistance
of a representative specimen conducted by,
(a) The National Research Council of Canada,
(b) Underwriters' Laboratories of Canada,
or
(c) another approved testing laboratory;
"fire separation" means construction that is a barrier
against the spread of fire and smoke, every opening in which is
protected by closures, shafts or other approved means so that
openings are effectively sealed against the passage of smoke and
flame, rated in accordance with Table 1;
"fire wall" means a continuous, self-supporting, noncombustible
fire separation that has a fire resistance rating of at least
two hours and terminates on,
(a) the ground,
(b) an exterior wall surface,
(c) an exterior roof surface, and
(d) another fire wall;
"flammable liquid" means a liquid with a flash point
below 38°C and a vapour pressure of 280 kPa (absolute) at 38°C;
"floor area" means the area of any room, floor, or part
of a floor of a hotel, measured from the inside surface of the
walls which form its boundaries;
"grade" means the average level of the surface of the
ground at the outside walls of a hotel;
"heavy timber construction" means an approved type of
wood construction in which a degree of fire endurance is attained
by requiring minimum sizes for wood structural assemblies;
"height in storeys" means the number of storeys between
the roof of a hotel's uppermost storey and the floor of its first
storey;
"high-rise hotel" means a hotel 18m or more in height
above grade;
"hold-open device" means an electrically actuated hold-open
device, listed by Underwriters' Laboratories of Canada or another
approved testing laboratory, that automatically closes a fire
door or smoke door on activation of a fire alarm signal or on
power failure;
"interior finish materials" means materials that form
part of or are affixed to interior walls, ceilings, floors and
other exposed interior surfaces, including,
(a) wallpaper, plastic wall coverings, panelling,
veneers, and paints and sprayed coating material having a thickness
of more than 1.5mm,
but not including,
(b) baseboards, mouldings, trim, doors, windows,
door and window frames, chalkboards, notice boards, showcases,
paints and sprayed coating material having a thickness of 1.5mm
or less, heavy timber construction, skylights, skydomes, decorations,
drapes, furniture and lighting fixtures;
"noncombustible", when applied to a material or combination
of materials, means material that will pass an approved test for
determination of noncombustibility in building materials conducted
by,
(a) The Canadian Standards Association Testing
Laboratories,
(b) The National Research Council of Canada,
(c) Underwriters' Laboratories of Canada,
or
(d) another approved testing laboratory;
"noncombustible construction" means an approved type
of construction in which a degree of fire safety is obtained by
the use of noncombustible material for structural assemblies and
by limiting the amount of combustible material that is incorporated
in the building construction;
"occupant load" means the total number of persons that
may occupy a hotel or part thereof at any one time, based on the
allotment of a certain portion of the floor area for each person;
"panic hardware" means an approved bar or panel listed
by Underwriters' Laboratories of Canada or another approved laboratory
or an approved bar or panel extending at least two-thirds the
width of a door, placed at a height suitable for the service required,
at least 1.1m above the floor, and designed to cause the door
to open when a pressure of 90N or less is applied to the bar or
panel in the direction of egress;
"place of assembly" means a floor area that has an occupant
load based on 1.2m2 or less per person, as designated
in section 13;
"products of combustion detector" means a fire detector
designed to cause a fire alarm system to operate when the concentration
of air-borne combustion products exceeds a predetermined level;
"self-closing device" means a door-closer listed by Underwriters'
Laboratories of Canada, or another approved testing laboratory,
designed to return a door to the closed position on being opened;
"smoke alarm" means a fire detector designed to produce
an audible signal when the concentration of airborne combustion
products exceeds a predetermined level;
"smoke detector" means a products of combustion detector;
"standpipe and hose system" means a system of pipes and
hoses connected to a water supply for the purpose of applying
water to a fire;
"storage garage" means a part of a hotel used or intended
to be used for the storage of automobiles;
"total floor area" means the area of all floors of basements,
mezzanines, storeys and penthouses in a hotel, measured from the
inside surface of the exterior or boundary walls;
"unit of exit width" means 550mm, and 300mm added to
one or more full units of exit width shall be counted as one-half
unit of exit width;
"wired glass" means glass at least 6mm thick in which
a mesh structure of wire is imbedded and completely covered;
"wired glass screen" means a partition of steel or steel-clad
framing containing wired glass panels none of which have an area
exceeding .84m2.
(2) Wherever in this Regulation reference is made to
a hotel that,
(a) is constructed after a specific date,
"constructed" means that building operations have progressed to
the stage where excavation for the footings is complete; or
(b) exists on a specific date, "exists" means
that building operations have progressed beyond the stage where
excavation for the footings is complete.
2. In this Regulation,
°C means Celsius degrees
cm means centimetres
hr means hours
kg means kilograms
kPa means kilopascals
lx means Illuminations
m means metres
mm means millimetres
N means Newtons |