SYSTEM TYPE |
Reactive
Surface Area
Per 1ltr Water |
Visibility
During
Operation |
Operating
Temp Of
Auto Nozzles |
Operating
Sensitivity / Speed
(R.T.I) |
Water Usage
Average Per
Head LPM |
Run Time
From Water Storage
4 heads Operating |
Dual Systems
Life Safety
Support |
Density Of
Head Spacing
Up To 5m |
System
Design
Objective |
Smoke
Control
(Scrubbing) |
Installation
Height
Restriction |
Use on various types
of fire i.e liquid fat |
Life
Safety Sprinklers
BS 5306 Part 2
|
2m² |
Good |
57-68ºc |
Fast Response
3mm Bulbs
40-50 |
60 LPM |
60 Minutes |
Yes |
3-4m |
Fire Control |
Poor |
No |
No |
Residential
& Domestic
Sprinklers BS9251 |
2m² |
Good |
57-68ºc |
Fast Response
3mm Bulbs
40-50 |
60 LPM |
15 min Domestic
30min Residential |
No
Single Pump |
3-4m |
Fire Control |
Poor |
Yes 22m |
No |
LP-2000
Life Safety
Low Pressure Water
Mist
|
2500m² |
Good |
57-68ºc |
Extra Fast Response
2.5mm Bulbs
27-31
|
Varies
Dependant Upon
Ceiling Height
8.0-21 LPM |
15 min Domestic
30-60 min Residential
60 min Commercial |
Yes |
2-3m |
Fire Suppression
Extinguishment |
Good |
No |
Yes |
High
Pressure Fog
Systems
|
3000-6000m² |
Poor |
57-68ºc |
Extra Fast Response
2.5mm Bulbs
27-31 |
8 LPM |
30 Minutes |
Yes |
2-3m |
Fire Suppression
Extinguishment |
Very
Good |
Yes due to
water
velocities
approx 60m |
Yes |